Fault Recorders

Home/Fault Recorders
  • Application
    • The Platinum 2.5K Portable Multi-Function Recorder is packaged in a rugged case with quick connect interfaces for fast and simple field connection.
    • Interface cables are provided with shrouded banana jacks that couple easily with a variety of measurement CT’s and voltage scaling devices offering complete flexibility for power utility and industrial use.
    • High-speed sinusoid data for traditional fault recorder analysis
    • Slower speed data for disturbance or swing recording
    • Continuous logging of RMS and phasor data for disturbance monitoring
    • Steady-state logging of RMS and harmonic spectrum values
    • System frequency for power quality analysis
    Inputs Number of Channels
    • 8 analog and 16 digital Voltage Inputs
    • 63.5 or 110 V RMS nominal
    • 480 or 600V RMS nominal (via external box) Current Inputs
    • 1 A or 5 A RMS nominal (thru current transformers, other ranges available) Frequency Response
    • DC – 1/2 sampling rate (1/4 sampling rate for 384 samples per cycle only) Accuracy
    • Better than 0.1% of full scale Digital Inputs
    • 24/48/125/250 VDC normally open or closed wetted contact
    SYSTEM TIMING Time Source
    • Optional internal GPS receiver with 1 PPS output for phasor measurement Accuracy
    • Normally better than +/- 60 ns
    ENCLOSURE Case and Unit
    • 30 lbs. (DIM)
    Details
  • Application The AMETEK TR-100+ is a fully featured Digital Fault Recorder with the capability to capture and analyze short transient events, longer-term disturbances and trend input quantities such as RMS, frequency, harmonics, power and power factor. Specifications INPUTS Number of Channels • 8, 16, 24, or 32 analog
    • 16, 32, 48, or 64 digital (larger systems available) Voltage Inputs
    • 57 to120 V RMS nominal, 212 V RMS full scale Current Inputs
    • 1 A or 5 A RMS nominal (thru external current shunts/CICT’s) Frequency Response • DC to 3,000 Hz, (+0dB, -3dB) or 1/4 sample rate Accuracy
    • Better than 0.2% full scale Digital Inputs • 24-250 VDC normally open or normally closed wetted contact
    SYSTEM TIMING Time Synchronization
    • Internal clock, synched to the 50/60 Hz line or optional IRIG-B
    Details
  • Application • For all types of power system events • Simultaneously perform: transient recording, disturbance recording, phasor measurements, power quality analysis, and sequence of events recording. • The system can operate automatically to retrieve events and perform an expert analysis so you have the answers fast, saving time and money. • Providing all the answers in one software platform. • The TR-2000 is ideally suited for your generation, transmission, and distribution power system monitoring.
    Details
  • Application
    • Fault and Disturbance Recorder
    • Transient Fault Location
    • Phasor Measurement Unit
    • Power Quality Monitor
    • Sequence of Events Recorder
    Specifications INPUTS Analog Inputs
    • Built in DSP for computations
    • 16 bits, 32768 levels (15 plus sign)
    • Fixed 512 samples/cycle (26KHz/31KHz)
    • Accuracy better than 0.1% of reading down to 3% of full scale Voltage Input Ranges
    • 1.414, 10, 150, 300V RMS full-scale or custom range (AC or DC compatible) Current Input Ranges
    • 1 A or 5 A RMS nominal (thru current shunts/CICT’s) Frequency Response
    • DC-1/2 sampling rate Digital Inputs
    • 24 to 250 VDC normally open or closed wetted contact Input Module
    • 6 analog (current or voltage) and 12 digital Inputs System Capacity (1-6 Input Modules)
    • 6, 12, 18, 24, 30 or 36 analog
    • 12, 24, 36, 48, 60 or 72 digital (multiple units tied together for larger systems)
    SYSTEM TIMING Time Synchronization Accuracy
    • 1 usec. or better
    • Internal GPS receiver
    • IRIG-B (Mod & TTL)
    • Network Time Protocol (NTP)
    ENCLOSURE Chassis
    • 4U (7”) 19” chassis mount
    CERTIFICATIONS CE  
    Details

Title